System Specifications for Cooling
The Johnson Air Rotation® System Cooling Guide Specification provides all of the information you need for brand new installations as well as retrofit projects for warehouses, distribution centers, manufacturing facilities, and other large, open buildings.
| Fact Sheet |
|
Cooling Only Guide Specification
The cooling system shall consist of a Johnson Air Rotation® System custom designed
and manufactured by Johnson MarCraft of St. Louis, Missouri. The equipment shall be
located per agreement between Johnson MarCraft and the end user.
General Information
The entire unit assembly shall be approved, listed and labeled by Underwriter’s
Laboratories (UL®). The Air Rotation® units shall be tested by the manufacturer and
incorporate the following:
Air Mover and Inlet Module
The Air Base includes custom designed cooling coils, filters, and stainless steel drain
pans to suit the individual unit location.
The unit shall have a 25" x 39" lockable access door. A "Warning Placard" shall be
affixed at the access door indicating that the unit is to be shut off before opening the door
and entering the fan compartment.
The air fans shall be equipped with dual belt drives with the drives selected for not less
than 400% of the horsepower rating. All belts on the unit shall be of the industrial grip
notch type selected for extended service life.
The unit manufacturer shall conduct sound testing in its manufacturing facility and certify
said testing is at 80 decibels or less.
Cooling coils and drain pans shall be mounted at floor level for ease of maintenance and
inspection. Cooling coils shall use 0.020” copper tubes and 0.0075” aluminum fins.
Standard: ARI 410 rated DX Type or Chilled Water Type Cooling Coils. Coil casings
shall be 16-gauge galvanized steel. The drain pans shall be triple pitched for complete
drainage and be constructed of all welded 304 stainless steel. Intermediate drain pans
shall have a copper downspout to the lower drain pan. The drain pan connection shall be
a minimum of 6" (152 mm) above the unit base for trapping. Face velocity of cooling
coils shall not exceed 500 fpm. The floor-level drain pan shall have a steel, walk-in grate
used for cleaning, service and maintenance purposes.
Filters: (Type 1): Pleated type, average efficiency of 25% - 30%, with average arrestance
of 90% - 92% in accordance with ASHRAE 52 Test Standard. Maximum Face Velocity:
500 fpm (2.54 m/s). Depth: 2" (51 mm) deep. UL Classification: Class 2. Filters: Nonwoven
cotton and synthetic fabric type manufactured by Farr, American Air Filter or
Continental Filters. Filters shall be mounted in slide tracks at ground or floor level for
ease of inspection and changing without access doors or other restrictions.
Filters: (Type 2): Washable aluminum mesh. Maximum Face Velocity: 600 fpm (3.05
m/s). Depth: 2" (51 mm) deep. Filters shall be mounted in slide tracks at floor or ground
level for ease of inspection and changing without access doors or other restrictions.
Power and Control Panels
There shall be a power panel containing 3-phase wiring.
The power panel shall have a locking dead front main power cabinet with disconnect and
containing necessary fuses, sub-circuits, magnetic starters with 3-leg protection, relays
and contactors requiring only single 3-phase connection.
The control panel shall contain a fan control switch allowing selection of continuous
multiple fan operation in either ventilation, cooling, or off positions.
Air Outlet Module
The Air Outlet Module shall be custom designed by Johnson MarCraft to ensure
appropriate air discharge at the designated location using both horizontal and vertical,
adjustable louvers, to direct discharge.
The discharge shall include turning vanes to minimize static loss within the unit and to
assist in the directional discharge. Turning vanes shall be designed to direct air toward
the applicable sides of discharge.
The unit shall be supplied with outlet extensions, which will be shipped to the jobsite as
four flat panels to be bolted together at the jobsite. The outlet extensions will be
designed to elevate the unit outlet as shown on the drawings, or above any obstructions
in the space.
General Comments
All flat panels used in unit manufacture shall be 18-gauge steel.
All solid panel portions of the air mover and inlet module shall have sound insulation
installed.
All unit modules shall be assembled with flat bar screwed in place and either grill or solid
panel. The grill and solid panel sections are easily removed to allow access to the
interior of the unit. Combustible materials may be placed or stored as close as 18 inches
from the entire unit assembly.
The unit manufacturer shall conduct sound testing in its manufacturing facility and certify
that the sound result is at 80 decibels or lower.
Technical Field Service
Incidental to the sale of this equipment, the services of a factory trained Field Engineer
will be provided at no added cost to supervise placing the System in operation and good
adjustment. The Field Engineer will instruct the owner's personnel in equipment
operation, and review maintenance procedures with the owner's qualified personnel or
qualified representatives. |